60W/120W/240W CliQ II series 24V Expand

60W/120W/240W CliQ II series 24V

DELTAPSU DELTAPSU

Uus

TELLIMISEL, küsi tarneaega

74,88 €

Nominal Output Voltage24V24V24V
Output Voltage Adjustment Range24V-28Vdc24-28Vdc24-28Vdc
Nominal Output Current2.5A5A10A
Output Power60W120W240W
Line Regulation< 0.5% typ. (@ 320-600Vac input, 100% load)< 0.5% Typical (@ 320-600Vac input, 100% load)< 0.5% typ. (@ 320-600Vac input, 100% load)
Load Regulation< 1% typ. (@ 320-600Vac input, 0-100% load)< 1% Typical (@ 320-600Vac input, 100% load)< 1% typ. (@ 320-600Vac input, 0-100% load)
PARD< 150mVpp< 50mVpp< 150mVpp
Start-up Time< 1,000ms @ nominal input (100% load)< 1,000ms @ nominal input (100% load)< 1,000ms @ nominal input (100% load)
Holdup Time> 20ms @ 3 x 400Vac
> 40ms @ 3 x 500Vac (100% load)
> 20ms @ 3 x 400Vac
>40ms @ 3 x 500Vac (100% load)
> 20ms @ 3 x 400Vac,
> 40ms @ 3 x 500Vac (100% load)
Dynamic Response± 5% @ 0-100% load± 5% @ 0-100% load± 5% @ 0-100% load
Start-up with Capacitive Loads10,000µF Max10,000µF Max10,000µF Max
Parallel ConnectionNoNoNo
Series ConnectionNoNoNo
Residual Ripple/PARD(20MHz)< 150mVpp
Nominal Input Voltage3 x 400-500Vac3 x 400-500Vac3 x 400-500Vac
Input Voltage Range320-600Vac 450-800 Vdc320-600Vac 450-800 Vdc320-600Vac 450-800 Vdc
Nominal Input Frequency50-60Hz50-60Hz50-60Hz
Input Frequency Range47-63Hz47-63Hz47-63Hz
Nominal DC Input Voltage500Vdc500Vdc
DC Input Voltage Range450-800Vdc
Input Current< 0.30A @ 3 x 400Vac,
< 0.25A @ 3 x 500Vac
< 0.50A @ 3 x 400Vac,
< 0.40A @ 3 x 500Vac
< 0.75A @ 3 x 400Vac,
< 0.65A @ 3 x 500Vac
Efficiency at 100%> 86.0% @ 3 x 400Vac & 3 x 500Vac> 87.0% @ 3 x 400Vac & 86% @ 3 x 500Vac> 92.0% @ 3 x 400Vac & 3 x 500Vac
Max. Inrush Current< 30A @3 x 400Vac & 3 x 500Vac< 30A @ 3 x 400Vac & 3 x 500Vac< 40A @ 3 x 400Vac & 3 x 500Vac
Power FactorConform to EN61000-3-2Conform with EN61000-3-2
Leakage Current< 3.5mA @ 500Vac< 3.5mA @ 500Vac< 3.5mA @ 500Vac
Case Chassis / Case CoverAluminiumAluminiumAluminium
Dimension121 x 50 x 117.3 mm
4.76" x 1.97" x 4.62"
121 x 50 x 117.3 mm
4.76" x 1.97" x 4.62"
121 x 70 x 117.3 mm
4.76" x 2.76" x 4.62"
Unit Weight0.66 kg0.66 kg0.89 kg
Cooling SystemConvectionConvectionConvection
Input Terminal4 Pins (Rated 600V/35A)4 Pins (Rated 600V/35A)4 Pins (Rated 600V/35A)
Output Terminal4 Pins (Rated 300V/28A)4 Pins (Rated 300V/28A)4 Pins (Rated 300V/28A)
Noise Sound Pressure Level (SPL)< 40dBA< 40dBA< 40dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715Standard TS35 DIN Rail in accordance with EN60715Standard TS35 DIN Rail in accordance with EN 60715
WireAWG 18-12AWG 18-12Input: AWG 18-12
Output: AWG 16-12
Operating Ambient Temperature-25°C to +80°C (Cold Start at -40°C)-25°C to +75°C-25°C to +80°C
Storage Ambient Temperature-40°C to +85°C-25°C to +85°C-25°C to +85°C
Power De-ratingVertical Mounting
> 50°C de-rate power by 2.5% /°C
> 70°C de-rate power by 5%/°C

Horizontal Mounting
> 45°C Derated power by 2.5% / °C
> 55°C Derated power by 1.66% / °C
>70°C Derated power by 5% / °C
Vertical Mounting
>50°C de-rate power by 2.5% / °C
>70°C de-rate power by 5% / °C

Horizontal Mounting
>40°C Derated power by 2.5% / °C
>60°C Derated power 5% / °C
> 50°C de-rate power by 2.5% / °C ,
>70°C de-rate power by 5% / °C
Operating Humidity< 95% RH (Non-Condensing)< 95% RH (Non-Condensing)0 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, 30G (300m/SІ) for a duration of 18ms, 1 times per direction, 2 times in totalIEC 60068-2-27, 30G (300m/SІ) for a duration of 18ms, 1 times per direction, 2 times in totalIEC 60068-2-27, 30G (300m/SІ) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration Test (Non-Operating)IEC 60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis for all X, Y, Z directionIEC 60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis for all X, Y, Z directionIEC 60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis for all X, Y, Z direction
Overvoltage Protection< 32V, ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)< 32V, ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)< 32V, ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload/Overcurrent Protection> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature Protection< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit ProtectionHicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Against ShockClass I with Primary Earth connectionClass I with Primary Earth connectionClass I with Primary Earth connection
MTBF> 800,000 hrs. as per Telcordia SR-332
I/P: 3 x 400Vac, O/P: 100% load, Ta: 25°C
> 500,000 hrs. as per Telcordia SR-332> 500,000 hrs. as per Telcordia SR-332
Electrical safetyUL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
ITESIQ to EN 60950-1,
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E191395),
CB scheme to IEC 60950-1
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E191395), CB scheme to IEC 60950-1SIQ to EN 60950-1, UL/cUL recognized to UL60950-1 and CSA C22.2 No. 60950-1 (File no. 191395),
CB scheme to IEC60950-1
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/ECIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/ECIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Galvanic IsolationInput to Output 4.0KVac
Input to Ground 2.0KVac
Output to Ground 1.5KVac
Input to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
Input to Output 4.0KVac
Input to Ground 2.0KVac
Output to Ground 1.5KVac
EmissionFCC Title 47, Class B / EN55022, CISPR22, CISPR11, Class BFCC Title 47, Class B / EN55022, CISPR22, CISPR11, Class BFCC Title 47, Class B / EN55022, CISPR22, CISPR11, Class B
ImmunityEN61000-4-2,1995;EN61000-4-4,1995; EN61000-4-5,1995;IEC61000-4-12 or IEEE C62.41;EN61000-4-3,1998;EN61000-4-8;EN61000-4-6,1996;EN61000-4-2,1995;EN61000-4-4,1995; EN61000-4-5,1995;IEC61000-4-12 or IEEE C62.41;EN61000-4-3,1998;EN61000-4-8;EN61000-4-6,1996;EN61000-4-2,1995;EN61000-4-4,1995; EN61000-4-5,1995;IEC61000-4-12 or IEEE C62.41;EN61000-4-3,1998;EN61000-4-8;EN61000-4-6,1996;
Voltage DipsConform to EN61000-4-11Conform to EN61000-4-11Conform to EN61000-4-11
CATEGORYpower adapter

Delta Electronics Group is a multi-billion dollar global company and the world’s leading producer of power supplies for the top names in industrial, medical and consumer electronics devices. For more than 40 years, Delta has been a well regarded and tr