60W CliQ II series 24V/48V Expand

60W CliQ II series 24V/48V

DELTAPSU DELTAPSU

Uus

TELLIMISEL, küsi tarneaega

44,16 €

Nominal Output Voltage24V48V
Output Voltage Adjustment Range24-28Vdc48-56Vdc
Nominal Output Current2.5A1.25A
Output Power60W60W
Line Regulation< 0.5% typ. (@ 85-264Vac input, 100% load)< 0.5% typ. (@ 85-264Vac input, 100% load)
Load Regulation< 1% typ. (@ 85-264Vac input, 0-100% load)< 1% typ. (@ 85-264Vac input, 0-100% load)
Start-up Time< 2000ms @ nominal input (100% load, 25°C)< 1,5 00ms @ nominal input (100% load )
Holdup Time> 20ms @ 115Vac,
> 125ms @ 230Vac (100% load, 25°C)
> 20ms @ 115Vac,
> 125 ms @ 230Vac (100% load )
Dynamic Response± 5% @ 0-100% load
Start-up with Capacitive Loads8,000µF Max
Parallel ConnectionNoNo
Series ConnectionNoNo
Nominal Output Voltage48Vdc
Residual Ripple/PARD(20MHz)< 200mVpp
Nominal Input Voltage100-240Vac100-240Vac
Input Voltage Range85-264Vac 120-375 Vdc85-264Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz47-63Hz
Nominal DC Input Voltage125-250Vdc125-250Vdc
DC Input Voltage Range120-375Vdc
Input Current< 1.40A @ 115Vac,
< 0.80A @ 230Vac
< 1.40A @ 115Vac,
< 0.80A @ 230Vac
Efficiency at 100%>90% @115Vac&230Vac> 91.0% @ 115Vac,
< 0.80A @ 230Vac
Max. Inrush Current< 20A @ 115Vac,
< 35A @ 230Vac
< 20A @ 115Vac,
< 35A @ 230Vac
Power FactorConform with EN61000-3-2Conform to EN 61000-3-2
Leakage Current< 1mA @ 240Vac< 1mA @ 240Vac
Case Chassis / Case CoverAluminiumAluminium
Dimension121 x 32 x 125 mm
4.76" x 1.26" x 4.92"
121 x 32 x 125 mm
4.76" x 1.26" x 4.92"
Unit Weight0.37 kg0.38 kg
Cooling SystemConvectionConvection
Input TerminalPluggable Connector 3 Pins (Rated 300V/15A)
Output TerminalPluggable Connector 2 Pins (Rated 300V/15A)
Operating Ambient Temperature-25°C to +80°C (Cold Start at -40°C)-20°C to +75°C
Storage Ambient Temperature-40°C to +85°C-25°C to +85°C
Power De-rating> 50°C de-rate power by 2.5% /°C> 50°C de-rate power by 2.5% /°C
Operating Humidity5 to 95% RH (Non-Condensing)< 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in totalIEC60068-2-27 , 30G (300m/S ² ) for a duration of 18ms , 1 times per direction, 2 times in total
Vibration Test (Non-Operating)IEC60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z directionIEC60068-2-6, 10Hz to 50 0Hz @ 3 0m/S² ( 3 G peak); 6 0 min per axis for all X, Y, Z direction
Overvoltage Protection< 32V ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)< 57 V, SELV Output, Hicc - up Mode , Non - Latching (Auto - Recovery)
Overload/Overcurrent Protection> 150% of rated load current, Hicc-up Mode,Non-Latching (Auto-Recovery)> 150 % of rated load current, Hicc - up Mode, Non - Latching (Auto - Recovery)
Over Temperature Protection< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 80 °C Surrounding Air Temperature @ 100% load, Non - Latching (Auto - Recovery)
Short Circuit ProtectionHicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hicc - up Mode, Non - Latching (Auto - Recovery when the fault is removed)
Degree of ProtectionIP20IP20
Protection Against ShockClass I with Primary Earth connectionClass I with PE* connection
MTBF> 1,000,000 hrs. as per Telcordia SR-332> 1,000,000 hrs, as per BELL CORE STD or IEC61790
Electrical safetyUL/cUL listed to UL508 and CSA C22.2 No. 107.1-01 (File No. E315355), 
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
SIQ to EN 60950-1, 
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, 
CB scheme to IEC 60950-1
ITETUV to EN 60950-1,
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395),
CB scheme to IEC 60950-1
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC 
For DRP024V060W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Galvanic IsolationInput to Output: 4.0KVac
Input to Ground: 1.5KVac
Output to Ground: 1.5KVac
Input to Output: 4.0KVac
Input to Ground: 1.5KVac
Output to Ground: 1.5KVac
EmissionCISPR22, EN55022, EN55011, FCC Title 47: Class BCISPR22, EN55022, EN55011, FCC Title 47: Class B
ImmunityEN55024: 1998/A1:2001/ A2:2003 Level 3; EN61000-4-2, Level 4 “Criteria A”EN55024, EN61000-6-1, EN61000-6-2
Voltage Fluctuation and FlickerIEC/EN 61000-3-3
CATEGORYpower adapter

Delta Electronics Group is a multi-billion dollar global company and the world’s leading producer of power supplies for the top names in industrial, medical and consumer electronics devices. For more than 40 years, Delta has been a well regarded and tr