480W/960W CliQ II series 24V Expand

480W/960W CliQ II series 24V

DELTAPSU DELTAPSU

New

by ORDER, ask for delivery time

159,36 €

Nominal Output Voltage24V24V
Output Voltage Adjustment Range24-28V24-28Vdc
Nominal Output Current20A40A
Output Power480W960W
Line Regulation< 0.5% typ. (@ 3 x 320-600Vac input, 100% load)< 0.5% typ. (@ 3 x 320-600Vac input, 100% load)
Load Regulation< 1% typ. (@ 3 x 320-600Vac input, 0-100% load)< 1% typ. (@ 3 x 320-600Vac input, 0-100% load)
PARD< 150mVpp< 240mVpp
Start-up Time< 1,000ms @ nominal input (100% load)< 1,500ms @ nominal input (100% load)
Holdup Time> 20ms @ 3 x 400Vac & 3 x 500Vac (100% load)> 20ms @ 3 x 400Vac & 3 x 500Vac (100% load)
Dynamic Response± 5% @ 10-90% load (@ 3 x 320-575Vac)
± 5% @ 15-90% load (@ 3 x 575-600Vac)
± 5% @ 10-100% load (@ 3 x 320-600Vac)
Start-up with Capacitive Loads10,000µF Max10,000μF Max
Parallel ConnectionNoNo
Series ConnectionNoNo
Nominal Input Voltage3 x 400-500Vac3 x 400-500Vac
Input Voltage Range320-600Vac 450-800 Vdc320-600Vac 450-800Vdc
Nominal Input Frequency50-60Hz50-60Hz
Input Frequency Range47-63Hz47-63Hz
Nominal DC Input Voltage500Vdc500Vdc
Input Current< 1.00A @ 3 x 400Vac
< 0.75A @ 3 x 500Vac
< 1.70A @3 x 400Vac,
< 1.40A @ 3 x 500Vac
Efficiency at 100%> 91.0% @ 3 x 400Vac & 3 x 500Vac> 92.0% @ 3 x 400Vac & 3 x 500Vac
Max. Inrush Current< 50A @ 3 x 400Vac & 3 x 500Vac< 40A @ 3 x 400Vac & 3 x 500Vac
Power Factor> 0.95 @ 3 x 400Vac,
> 0.94 @ 3 x 500Vac
> 0.95 @ 3 x 400Vac,
> 0.94 @ 3 x 500Vac (at 100% load)
Leakage Current< 3.5mA @ 3 x 600Vac< 3.5mA @ 3 x 600Vac
Case Chassis / Case CoverAluminiumAluminium
Dimension121 x 140 x 117.3 mm
4.76" x 5.51" x 4.62"
121 x 255 x 117.3 mm
4.76" x 10.04" x 4.62"
Unit Weight1.35 kg2.60 kg
Cooling SystemConvectionConvection
Input Terminal4 Pins (Rated 600V/35A)4 Pins (Rated 600V/35A)
Output Terminal4 Pins (Rated 300V/30A)6 Pins (Rated 300V/30A)
Noise Sound Pressure Level (SPL)< 40dBA< 40dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715Standard TS35 DIN Rail in accordance with EN 60715
WireInput: AWG 18-8
Output: AWG 12-10
Input: AWG 18-8
Output: AWG 12-10
Operating Ambient Temperature-25°C to +80°C-25°C to +65°C
Storage Ambient Temperature-25°C to +85°C-25°C to +85°C
Power De-rating> 50°C de-rate power by 2.5% / °C ,
> 70°C de-rate power by 5% / °C
Vertical Mounting > 50°C de-rate power by 2.5% / °C
Operating Humidity5 to 95% RH (Non-Condensing)5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, 30G (300m/S for a duration of 18ms, 3 times per direction, 6 times in totalIEC 60068-2-27, 30G (300m/SІ) for a duration of 18ms, 2 times per direction, 1 times in total
Vibration Test (Non-Operating)IEC 60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis for all X, Y, Z directionIEC 60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis for all X, Y, Z direction
Overvoltage Protection< 32V, ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)< 32V, ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload/Overcurrent Protection> 200% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature Protection< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 65°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit ProtectionHicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIP20IP20
Protection Against ShockClass I with Primary Earth connectionClass I with Primary Earth connection
MTBF> 500,000 hrs. as per Telcordia SR-332> 300,000 hrs. as per Telcordia SR-332
I/P: 3 x 400Vac, O/P: 100% load, Ta: 25°C
Electrical safetyUL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
ITESIQ to EN 60950-1,
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E191395),
CB scheme to IEC 60950-1
SIQ to EN 60950-1,
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E191395),
CB scheme to IEC 60950-1
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/ECIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Safety ApprovalsSIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Galvanic IsolationInput to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
Input to Output 4.0KVac
Input to Ground 2.0KVac
Output to Ground 1.5KVac

EmissionCISPR 22, EN 55022, CISPR 11, EN 55011, FCC Title 47: Class B
ImmunityEN 61000-4-2, 1995; EN 61000-4-4, 1995; EN 61000-4-5, 1995; IEC 61000-4-12 or IEEE C62.41; EN 61000-4-3, 1998; EN 61000-4-8; EN 61000-4-6, 1996
Radiated ImmunityIEC 61000-4-3; Level 3 Criteria A
80MHz-1GHz, 10V/M, 80% modulation (1KHz)
1.4GHz-2GHz, 3V/M, 80% modulation (1KHz)
2GHz-2.7GHz, 1V/M, 80% modulation (1KHz)
SurgeIEC 61000-4-5; Level 3 Criteria A
Common Mode: 2kV
Differential Mode: 1kV
Conducted ImmunityIEC 61000-4-6; Level 3 Criteria A, 150kHz-80MHz, 10Vrms
Voltage DipsIEC 61000-4-11; 100% dip; 1 cycle (20ms); Self Recoverable
CATEGORYPower supply adapter

Delta Electronics Group is a multi-billion dollar global company and the world’s leading producer of power supplies for the top names in industrial, medical and consumer electronics devices. For more than 40 years, Delta has been a well regarded and tr