120W CliQ II series 24V/48V Expand

120W CliQ II series 24V/48V

DELTAPSU DELTAPSU

New

by ORDER, ask for delivery time

67,20 €

Nominal Output Voltage24V48V
Output Voltage Adjustment Range24-28Vdc48-56Vdc
Nominal Output Current5A2.5A
Output Power120W120W
Line Regulation< 0.5% typ. (@ 85-264Vac input, 100% load)< 0.5% typ. (@ 85-264Vac input, 100% load)
Load Regulation< 1% typ. (@ 85-264Vac input, 0-100% load)< 1% typ. (@ 85-264Vac input, 0-100% load)
Start-up Time< 1000ms @ nominal input (100% load, 25°C)< 2,000ms @ nominal input (100% load)
Holdup Time> 20ms @ 115Vac,
> 115ms @ 230Vac (100% load, 25°C)
> 20ms @ 115Vac, 
> 50ms @ 230Vac (100% load)
Dynamic Response± 5% @ 0-100% load± 2% @ 0-100% load
Start-up with Capacitive Loads10,000µF Max6,500μF Max
Parallel ConnectionNoNo
Series ConnectionNoNo
Residual Ripple/PARD(20MHz)< 50mVpp/ < 150mVpp @ 25°C< 200mVpp
Nominal Input Voltage100-240Vac100-240Vac
Input Voltage Range85-264Vac 120-375 Vdc85-264Vac
Nominal Input Frequency50-60Hz50-60Hz
Input Frequency Range47-63Hz47-63Hz
Nominal DC Input Voltage125-250Vdc125-250Vac
DC Input Voltage Range120-375Vdc
Input Current< 2.20A @ 115Vac,
1.20A @ 230Vac
< 2.2A @ 115Vac, < 1.1A @ 230Vac
Efficiency at 100%> 89.0% @ 115Vac,
> 90.0% @ 230Vac
> 90.0% @ 115Vac, > 91.0% @ 230Vac
Max. Inrush Current< 35A @ 115Vac & 230Vac< 35A @ 115Vac & 230Vac
Power FactorConform with EN61000-3-2> 0.99 @ 115Vac,
> 0.93 @ 230Vac
Leakage Current< 1mA @ 240Vac< 1mA @ 240Vac
Case Chassis / Case CoverAluminiumAluminium
Dimension121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"
121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"
Unit Weight0.72 kg0.72 kg
Cooling SystemConvectionConvection
Input TerminalPluggable Connector 3 Pins (Rated 300V/15A)Pluggable Connector 3 Pins (Rated 300V/15A)
Output TerminalPluggable Connector 4 Pins (Rated 300V/15A)Pluggable Connector 4 Pins (Rated 300V/15A)
Noise Sound Pressure Level (SPL)< 40dBA< 40dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN60715Standard TS35 DIN Rail in accordance with EN 60715
WireInput: AWG 20-12
Output: AWG 20-12
AWG 20-12
Operating Ambient Temperature-25°C to +80°C (Cold Start at -40°C)-25°C to +80°C (Cold Start at -40°C)
Storage Ambient Temperature-40°C to +85°C-40°C to +85°C
Power De-rating> 50°C de-rate power by 2.5% / °C> 50°C de-rate power by 2.5% / °C
Operating Humidity5 to 95% RH (Non-Condensing)5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC60068-2-27, 30G (300m/SІ) for a duration of 18ms, 1 time per direction, 2 times in totalIEC60068-2-27, 30G (300m/SІ) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration Test (Non-Operating)IEC60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis for all X, Y, Z directionIEC 60068-2-6, 10Hz to 500Hz @ 30m/SІ (3G peak); 60 min per axis 
for all X, Y, Z direction
Overvoltage Protection< 32V ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)> 57V, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
Overload/Overcurrent Protection> 150% of rated load current, Hicc-up Mode,Non-Latching (Auto-Recovery)> 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
Over Temperature Protection< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit ProtectionHicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIP20IP20
Protection Against ShockClass I with Primary Earth connectionClass I with Primary Earth connection
MTBF> 800,000 hrs. as per Telcordia SR-332> 800,000 hrs. as per Telcordia SR-332 
I/P: 115Vac, O/P: 100% load, Ta: 25°C
Electrical safetyUL/cUL listed to UL508 and CSA C22.2 No. 107.1-01 (File No. E315355), 
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355), 
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
ITESIQ to EN 60950-1, 
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), 
CB scheme to IEC 60950-1
SIQ to EN 60950-1, 
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), 
CB scheme to IEC 60950-1
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
For DRP024V120W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC 
For DRP048V120W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Galvanic IsolationInput to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
Input to Output 4.0KVac 
Input to Ground 1.5KVac 
Output to Ground 1.5KVac

EmissionCISPR22, EN55022, EN55011, FCC Title 47: Class BCISPR 22, EN 55022, CISPR 11, EN 55011, FCC Title 47: Class B
ImmunityEN55024: 1998/A1:2001/ A2:2003 Level 3; EN61000-4-2, Level 4 “Criteria A”EN 55024, EN 61000-6-1, EN 61000-6-2
Voltage DipsConform to EN61000-4-11
CATEGORYPower supply adapter

Delta Electronics Group is a multi-billion dollar global company and the world’s leading producer of power supplies for the top names in industrial, medical and consumer electronics devices. For more than 40 years, Delta has been a well regarded and tr