120W/240W/480W CliQ series 24V Expand

120W/240W/480W CliQ series 24V

DELTAPSU DELTAPSU

New

by ORDER, ask for delivery time

46,66 €

Nominal Output Voltage24V24V24V
Output Voltage Adjustment Range22-28Vdc22-28Vdc22-28Vdc
Nominal Output Current5A10A20A
Output Power120W240W480W
Line Regulation< 0.5% typ. (@ 85-264Vac input, 100% input)< 0.5% typ. (@ 85-264Vac input, 100% input)< 0.5% typ. (@ 85-264Vac input, 100% input)
Load Regulation< 1% typ. (@ 85-264Vac input, 0-100% input)< 1% typ. (@ 85-264Vac input 0-100% input)< 1% typ. (@ 85-264Vac input, 0-100% input)
PARD< 240mVpp
Start-up Time< 1000ms @ nominal input (100% load)< 1000ms @ nominal input (100% load, 25°C)< 1,000ms @ nominal input (100% load)
Holdup Time> 35ms @ 115Vac(100% load)
> 70ms @ 230Vac (100% load)
> 20ms @ 115Vac & 230Vac (100% load, 25°C)> 20ms @ 115Vac & 230Vac (100% load)
Dynamic Response± 5% @ 85-264Vac input, 5-100% load 
(Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 1KHz)
± 5% @ 10-100% load± 5% @ 0-100% load
Start-up with Capacitive Loads10,000µF Max10,000µF Max10,000µF Max
Parallel ConnectionNoNoNo
Series ConnectionNoNoNo
Nominal Input Voltage100-240Vac100-240Vac100-240Vac
Input Voltage Range85-264Vac85-264Vac 120-375 Vdc85-264Vac 120-375 Vdc
Nominal Input Frequency50-60Hz50-60Hz50-60Hz
Input Frequency Range47-63Hz47-63Hz47-63Hz
Nominal DC Input Voltage125-250Vdc125-250Vdc
DC Input Voltage Range120-375 Vdc
Input Current< 1.40A @ 115Vac,
< 0.80A @ 230Vac
< 2.90 @ 115Vac,
< 1.50A @ 230Vac
< 5.70A @ 115Vac,
< 2.80A @ 230Vac
Efficiency at 100%> 86.0% @ 115Vac, > 87.0% @ 230Vac> 89.0% @ 115Vac,
> 91.0% @ 230Vac
> 85.0% @ 115Vac,
> 88.0% @ 230Vac
Max. Inrush Current< 80A @ 115Vac,
No Damage @ 230Vac
No Damage & IІt rating at all I/P device shall not exceed their rating< 50A @ 115Vac,
< 150A @ 230Vac
Power Factor> 0.98 @ 115Vac,
> 0.87 @ 230Vac
> 0.96@ 115Vac,
> 0.90 @ 230Vac
> 0.97@ 115Vac,
> 0.95 @ 230Vac
Leakage Current< 1mA @ 240Vac< 1mA @ 240Vac< 1.25mA @ 240Vac
Case Chassis / Case CoverAluminiumAluminiumAluminium
Dimension121 x 50 x 118.7 mm
4.76" x 1.97" x 4.67"
121 x 85 x 118.5 mm
4.76" x 3.35" x 4.67"
121 x 160 x 118.5 mm
4.76" x 6.30" x 4.67"
Unit Weight0.54 kg1.04 kg1.80 kg
Cooling SystemConvectionConvectionConvection
Input TerminalM4 x 3 Pins (Rated 300V/20A)M4 x 3 Pins (Rated 300V/20A)3 Pins (Rated 300V/20A)
Output TerminalM4 x 2 Pins (Rated 300V/20A)M4 x 2 Pins (Rated 300V/20A)4 Pins (Rated 300V/20A)
WireStandard TS35 DIN Rail in accordance with EN 60715
Operating Ambient Temperature-20°C to +80°C-20°C to +75°C-20°C to +80°C
Storage Ambient Temperature-25°C to +85°C-25°C to +85°C-25°C to +85°C
Power De-ratingVertical: > 50°C de-rate power by 2.5% /°C
Horizontal: > 50°C de-rate power by 2.5% / °C, > 70°C de-rate power by 4% / °C
> 50°C de-rate power by 2.5% /°C,
> 70°C de-rate power by 4% /°C
> 50°C de-rate power by 2.5% / °C
Operating Humidity5 to 95% RH (Non-Condensing)< 95% RH (Non-Condensing)5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, 30G (300m/SІ) for a duration of 18ms, 
3 times per direction, 18 times in total
IEC60068-2-27, 30G (300m/SІ) for a duration of 18msIEC 60068-2-27, 30G (300m/SІ) for a duration of 18ms, 3 times per direction, 6 times in total
Vibration Test (Non-Operating)IEC60068-2-6, 10Hz to 150Hz @ 50m/SІ (5G peak); 90 min per axis for all X, Y, Z directionIEC60068-2-6, 10Hz to 150Hz @ 50m/SІ (5G peak); 90 min per axis for all X, Y, Z directionIEC60068-2-6, 10Hz to 150Hz @ 50m/SІ (5G peak); 90 min per axis for all X, Y, Z direction
Overvoltage Protection32V +10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)32V +10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)32V ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload/Overcurrent Protection> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)> 200% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature Protection< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit ProtectionHicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIPX0
Protection Against ShockClass I without Primary Earth connectionClass I without Primary Earth connectionClass I without Primary Earth connection
MTBF> 500,000 hrs. as per Telcordia SR-332 
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
> 300,000 hrs. as per Telcordia SR-332> 300,000 hrs. as per Telcordia SR-332
I/P: 115Vac, O/P: 100% load, Ta: 25°C
Electrical safetySIQ Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (under alternate part number EOE12010002 of File No. E191395)
CSA: CSA C22.2 No. 60950-1 and UL 60950-1 (under alternate part number EOE12010002 of File No. 181564)
CB
UL/cUL listed to UL 508 and CSA C22.2 
No. 107.1-01 (under alternate part number EOE12010005 of File no. E315355),
CSA to CSA C22.2 No. 107.1-01
(under alternate part number EOE12010005 of File No. 181564)
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
(under alternate part number EOE13010007 of File no. E315355), CSA to CSA C22.2 No. 107.1-01 
(under alternate part number EOE13010007 of File No. 181564)
ITESIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 
No. 60950-1 (under alternate part number EOE12010005 of File no. E191395),
CSA to CSA C22.2 No. 60950-1 and UL 60950-1,
CB scheme to IEC 60950-1
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 
No. 60950-1 (under alternate part number EOE13010007 of File no. E191395),
CSA to CSA C22.2 No. 60950-1 and UL 60950-1,
CB scheme to IEC 60950-1
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/ECIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/ECIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Galvanic IsolationInput to Output: 4.0KVac
Input to Ground: 1.5KVac
Output to Ground: 1.5KVac
Input to Output: 4.0KVac,
Input to Ground: 1.5KVac,
Output to Gruond: 1.5KVac
Input to Output: 4.0KVac,
Input to Ground: 1.5KVac,
Output to Ground: 1.5KVac
EmissionCISPR22, EN55022, EN55011, FCC Title 47: Class BCISPR22, EN55022, EN55011, FCC Title 47: Class BCISPR22, EN55022, EN55011, FCC Title 47: Class B
ImmunityEN55024: 1998/A1:2001/ A2:2003 Level 3; EN61000-4-2, Level 4 “Criteria A”EN55024: 1998/A1:2001/ A2:2003 Level 3; EN61000-4-2, Level 4 “Criteria A”EN55024: 1998/A1:2001/ A2:2003 Level 3; EN61000-4-2, Level 4 “Criteria A”
CATEGORYPower supply adapter

Delta Electronics Group is a multi-billion dollar global company and the world’s leading producer of power supplies for the top names in industrial, medical and consumer electronics devices. For more than 40 years, Delta has been a well regarded and tr